Directional Sounders Part II - Code Requirements and Applications
Last  month’s issue featured  the first article in a series about exit marking directional sounders, in which  we discussed the purpose of these new devices, explained their development and  covered the basic acoustic principles on which they operate. This month’s  discussion goes a step further in defining their application.
  
  The horns/strobes/speakers normally tied into  a commercial fire alarm system are the code-required notification (located per  NFPA 72) audible and visible appliances used to alert a building’s occupants  for the need to evacuate or relocate within the building. Any device or  appliance that is not required by a code or standard is called “supplemental.”  One example includes directional sounders, which are not a replacement for the  code-required audible or visible notification appliances, but instead are  designed to be blended into the standard audible warning produced by horns,  bells or the voice evacuation message produced by speakers. 
  
  Supplemental also means that directional  sounders must be “sold” to the building owner or tenant and proposed for their  consideration as an improvement to evacuation efficiency in specific  circumstances.  In some cases,  directional sounders are not always useful or desirable. For example, leading  large numbers of occupants toward exits that cannot accommodate such a large  group at one time would certainly not enhance evacuation efficiency. Each  installation must be evaluated as to their applicability, based on the  manufacturer’s documentation and installation instructions. 
  
  Being a “supplemental” device doesn’t mean  the code is silent on these directional notification appliances. Section 7.4.6  of NFPA 72 provides the five basic requirements for directional sounders.
  
  “7.4.6 Exit Marking  Audible Notification Appliance Requirements.
  7.4.6.1* Exit marking  audible notification appliances shall meet or exceed the frequency and sound  level settings and guidelines specified in the manufacturer’s documented  instructions. 
  7.4.6.2* In addition to 7.4.6.1,  as a minimum, to ensure that exit marking audible notification appliance signals  are clearly heard and produce the desired directional effects for 15.24 m (50  feet) within an unobstructed egress path, they shall meet the audibility  requirements of 7.4.6.1, Narrow Band Tone Signaling for Exceeding Masked  Thresholds, in at least one octave band or one octave band within the effective  frequency ranges of the interaural time difference (ITD), interaural level or  intensity difference (ILD or IID) and anatomical transfer function or  head-related transfer function (ATF or HRTF) localization cues. The signal  shall penetrate both the ambient noise and the fire alarm signal. 
  7.4.6.3  Where required, exit marking audible  notification appliances shall be installed in accordance with the  manufacturer’s instructions. 
  7.4.6.4*  Where required, exit marking audible  notification shall be located at the entrance to all building exits and areas  of refuge as defined by the applicable building or fire code. 
  7.4.6.5 Where exit  marking audible notification appliances are utilized to mark areas of refuge, they  shall provide an audible signal distinct from that used for other exits that do  not have areas of refuge.”
  
  Additional directional sounders may be wired  into either a new or an existing notification appliance circuit [can be added  to most two-wire NACs] for systems using standard 24 volt DC regulated power  supplies (not FWR), keeping in mind that the same NAC wiring rules apply.
  
  Additional installation requirements  may include obtaining a permit, submitting  plans indicating the location of all notification appliances, and providing  specification sheets for all the existing and new appliances, as well as  voltage drop and standby battery calculations. 
  
For a basic Type 1 system/installation, look  for the illuminated exit signs in public buildings. Type 2 installations  consist of a typical Type 1 installation but include additional sounders to  provide an audible indication of the best egress path to lead occupants to  where they will hear the Type 1 directional sounder located at exit/refuge  areas.
Greg Kessinger, SET, CFPS, is the chair of the NBFAA’s Fire and Life Safety Committee. He can be reached at [email protected] or www.FireAlarm.org.
About the Author
